You are here:

Resistive Load Banks

Resistive Load Banks

Resistive load bank(AC Load Bank, Dummy Load Bank, Generator Load Bank,Load Bank for Generator Testing) is a device which can simulate the real-life resistive loads and provides a rigorous test regime for power supplies from 1kW to 60MW. The “load” of a resistive load bank is created by the conversion of electrical energy to heat by power resistors. It mainly used to test and maintenance of Engine Generators, Storage Battery Systems, UPS Systems, Inverters, Ground Power Units, Auxiliary Power Units, Aircraft Power Generators, Wind Generators, Hydro Generators etc.





Description

Introduction


Resistive load bank are available in stationary type for permanent installation(Permanent Load Bank) or portable type(Portable Load Bank) with lifting rings, castors. Larger load banks, typically above 1250KW, are based on an ISO container construction. Special finishes including custom paint colors and stainless steel casings can be supplied.


Main features 


1.Control mode: (1)local manual control panel (2)remote manual control box (3) remote console (include manual panel and PC control)(4)laptop control

2. Protection function: overvoltage, overcurrent, overheat, over low blowing rate, blower overheat, blower phase sequence reverse protection, smoke alarm etc.

3. Cooling: industrial heavy duty blower, horizon air intake, upwards outlet, low noise.

4. Power consumption components: made by special alloy resistance, high temperature resisting, high heat dissipation capability, high heat stability, no naked light, safety and reliability. Running temperature is 1/3 of rating.

5. Weather-proof structure: containerized structure provides ultra protection, protection grade higher than IP55.

6. Material and coating: the body adopt cold-rolled steel plate that processed by galvanizing corrosion protection, powder coated and spray paint.

7. Integrated & modularization design: easy to installation, maintenance and transportation.

 

Technical Parameters


 

Model

Power Factor

Load Voltage

Dimension
W*D*H(mm)

Weight(kg)

AC400-20kW

1

3 phase 400V 50HZ/60HZ

480*485*680

30

AC400-100kW

700*900*900

80

AC400-200kW

1200*1500*1500

200

AC400-500kW

1460*1980*1800

750

AC400-1000kW

1600*2400*2100

1500

AC400-2000kW

6058*2438*2591

5000

AC400-3000kW

7000

AC400-4400kW

8000